How the math works
Last updated
Every BackupPlanner calculator runs on the same set of formulas, and every result has a "Show the math" link that lists the steps. This page explains those formulas and lists every default number we assume. The list of assumptions at the bottom is generated from the same file the calculators use, so it can't drift out of date.
Four rules we follow
- Round toward safety. Runtimes and nights round down. Sizes, fuel and charge times round up.
- Show a range, not just a number. Appliances vary, so results come with a low-to-high range where we have the data.
- Name every assumption. If a number isn't from your input or a product's spec sheet, it's in the table below.
- Recommend by fit, never by commission. The code that ranks products can't see which stores pay us. See how we make money.
Running watts and starting watts
Running watts are what an appliance draws once it's going. Starting watts are the brief spike when a motor or compressor starts, often 2 to 3 times higher. Your power source has to cover both:
peak running watts = sum of running watts of everything on at once
peak starting watts = peak running watts + the biggest single (starting − running) jumpThis assumes only one motor starts at a time, the standard way to size a generator. Start big motors one by one. When we don't have an appliance's starting watts, we estimate them: 3× running watts for a compressor, 2.5× for a pump or blower motor, 1.2× for an inverter-drive compressor. The result says when it's an estimate.
Average power: why a fridge isn't on all the time
A fridge compressor or a sump pump switches on and off. Its duty cycle is the share of time it's actually running. Average power = running watts × duty cycle. A 150 W fridge at a 40% duty cycle averages 60 W. If an appliance has an Energy Star yearly kWh figure, we use that instead (yearly kWh × 1,000 ÷ 8,760 hours), because it comes from a real test.
A sump pump's duty is starts per hour × seconds per run ÷ 3,600. Ten 15-second runs an hour is about 4%.
Power station runtime
usable Wh = rated Wh × 95%
drain = average watts ÷ 90% inverter efficiency + inverter idle draw
runtime = usable Wh ÷ drainThe idle draw is what the inverter burns just by being switched on: we assume the larger of 5 W or 1% of the station's continuous rating. We keep it separate from efficiency because it matters most for small loads. A 1,000 Wh station running a 25 W CPAP may burn 10 to 15 W just keeping the inverter on; a flat "15% loss" would overstate the runtime badly.
If a device can run from the station's 12 V or USB-C port instead, there's no inverter and no idle draw: drain = average watts ÷ 90%. That's often a much longer runtime, so the CPAP calculator shows both.
Battery banks and lead-acid batteries
rated Wh = volts × amp-hours
usable Wh = rated Wh × depth of discharge × Peukert factorDepth of discharge is how much of the battery we plan to use: 90% for lithium iron phosphate (LiFePO4) and 80% for lead-acid in an emergency. Routine lead-acid use should stop at 50%.
Lead-acid batteries also deliver fewer amp-hours when you draw a lot of current (the Peukert effect). Their amp-hour rating is measured over 20 hours, so at higher current we scale it down:
Peukert factor = (amp-hour rating ÷ (20 × amps drawn)) ^ (k − 1), never more than 1k is 1.15 for AGM, 1.25 for flooded and 1.12 for gel batteries. LiFePO4 is treated as 1, which means no correction.
Battery backup sump pumps
Makers rarely publish their backup pump's amp draw, but they do publish a runtime claim such as "48 hours at a 10% duty cycle." That fixes how long the battery can pump without stopping:
continuous pumping hours = claimed hours × claimed duty (48 × 0.10 = 4.8 hours)
your runtime = continuous hours × 80% ÷ your pump's dutyWe count on 80% of the claim because it assumes a new, fully charged battery, and a battery that has sat on standby for a few years holds less. Try it in the Sump Pump Backup Calculator.
Generator size
running watts needed = peak running watts ÷ 80%
starting watts needed = peak starting watts
at altitude: divide both by (1 − 3.5% × thousands of feet above sea level)The 80% rule keeps you from running a generator flat out for hours. We then point you to the nearest common size class (2,000, 3,500, 5,000, 7,500, 9,500, 12,000 W). Dual-fuel generators are checked on each fuel separately, because propane ratings are usually about 10% lower.
Generator fuel use
A generator's fuel use rises in a straight line with load, but it never drops to zero:
load fraction = watts drawn ÷ rated running watts (at least 10%)
fuel per hour = full-load rate × (a + (1 − a) × load fraction)a is the share of full-load fuel it burns at no load: 40% for a conventional generator and 20% for an inverter generator, which throttles down. When the maker publishes two or more runtime claims (say "8.1 hours at 25% load" and "3.2 hours at full load"), we fit the line through those claims instead. When there's no claim at all, we fall back to a typical rate per rated kW from the list below and say so on the result.
Propane weighs 4.24 lb per gallon, and a full "20-lb" grill tank holds 20 lb. In cold weather (below about 20 °F) a 20-lb tank may not vaporize fast enough for a large generator.
Solar recharge
daily harvest = panel watts × peak sun hours × 75%The 75% covers heat, panel angle, dirt, wiring and charging losses. Real panels rarely deliver their rated watts.
Planning margins
When we recommend a size, it's 25% above what the math says you need, so a hot day or an aging battery doesn't leave you short. We don't pad runtime estimates; those round down instead. For medical devices such as a CPAP we recommend capacity for 2× the nights you ask for, and we never present a runtime as a guarantee. See our safety and medical notes.
How results are rounded
| Result | Rounded | Example |
|---|---|---|
| Runtime under 2 hours | down to 0.1 hour | 1.86 → 1.8 hours |
| Runtime 2–48 hours | down to 0.5 hour | 11.63 → 11.5 hours |
| Runtime over 48 hours | down to whole hours | 70.2 → 70 hours (about 2.9 days) |
| CPAP nights | down to 0.1 | 2.78 → about 2.7 nights |
| Watts needed | up to the next 50 W | 2,727 → 2,750 W |
| Fuel | up to 0.1 gal or lb | 8.33 → 8.4 gal |
| Capacity needed | up to the next 100 Wh | 1,312 → 1,400 Wh |
| Charge time | up to 0.5 hour or 0.5 day | 1.48 days → 1.5 days |
Every default assumption
These are the numbers we use when neither you nor the product's spec sheet gives us a better one. A product's own data (a maker's runtime claim, for example) always wins. The 7 marked to be measured are our best estimates until we can check them with our own power meter; see how we test.
Usable share of a power station 95%
Share of a power station's rated Wh you can actually draw: covers the battery management reserve and early cell aging.
Plausible range: 90–100%. Source: Independent discharge tests of LiFePO4 stations typically deliver 85–95% of rated Wh at the AC outlet, of which inverter loss is modelled separately.
Inverter efficiency 90%
DC to AC conversion loss at moderate load.
Plausible range: 85–94%. Source: Typical pure-sine inverter efficiency curves at 20–80% load.
Inverter idle draw 5 W (minimum)to be measured
Power the inverter burns just by being switched on: the larger of 5 W or 1% of the continuous rating. Matters most for small loads such as a CPAP or a sump pump on standby.
Plausible range: 5–35. Source: Estimate; no maker publishes it. To be measured with our meter (step 2.7).
Inverter idle draw, scaled to size 1% of continuous Wto be measured
Scales the idle draw with inverter size (see inverter idle draw).
Plausible range: 0.5–2%. Source: Estimate; to be measured (step 2.7).
DC port efficiency 90%
12 V car port or a device's own DC adapter: no inverter and no idle draw.
Plausible range: 85–95%. Source: Typical DC-DC converter efficiency.
Depth of discharge, LiFePO4 90%
Depth of discharge for a standalone LiFePO4 battery.
Plausible range: 80–100%. Source: LiFePO4 maker guidance (80–100% DoD rated).
Depth of discharge, lead-acid in an outage 80%
Lead-acid drawn down in an outage. Routine use should stop at 50%; deep cycles shorten its life.
Plausible range: 50–80%. Source: AGM and flooded battery maker guidance.
Peukert exponent, AGM 1.15
AGM batteries lose capacity at high current.
Plausible range: 1.1–1.2. Source: Typical AGM Peukert exponents.
Peukert exponent, flooded lead-acid 1.25
Flooded lead-acid loses more capacity at high current.
Plausible range: 1.2–1.3. Source: Typical flooded Peukert exponents.
Peukert exponent, gel 1.12
Gel batteries lose a little capacity at high current.
Plausible range: 1.07–1.17. Source: Typical gel Peukert exponents.
Generator load limit 80%
Don't plan to run a generator above 80% of its rated running watts for hours.
Plausible range: 75–85%. Source: Generator maker guidance; standard sizing practice.
Altitude derating 3.5% per 1,000 ft
Engine output drops about 3.5% for every 1,000 ft above sea level.
Plausible range: 3–4%. Source: Generator maker manuals (3–4% per 1,000 ft).
Fallback gas use, conventional generator 0.14 gal/h per rated kW at full load
Fallback fuel rate when a conventional generator has no runtime claim.
Plausible range: 0.12–0.16. Source: Calibrated 2026-11-17 against 3 Generac claims (0.119–0.151).
Fallback gas use, inverter generator 0.14 gal/h per rated kW at full load
Fallback fuel rate when an inverter generator has no runtime claim.
Plausible range: 0.09–0.17. Source: Calibrated 2026-11-17 against 11 Honda, Westinghouse and Generac claims (median 0.140).
Fallback propane use 0.85 lb/h per rated propane kW at full loadto be measured
Fallback propane rate when a generator has no propane runtime claim.
Plausible range: 0.75–1. Source: Estimate from typical spec sheets.
No-load fuel use, conventional generator 40% of full-load rate
A conventional generator at no load still burns about 40% of its full-load fuel rate.
Plausible range: 35–50%. Source: Spec-sheet runtime claims at 25/50/100% load.
No-load fuel use, inverter generator 20% of full-load rate
Inverter generators throttle down at light load (eco mode).
Plausible range: 17–25%. Source: Calibrated from Honda's two-point claims (EU2200i 0.19, EU3200i 0.18, EU7000iS 0.20).
Propane weight per gallon 4.24 lb/gal
Weight of a gallon of liquid propane.
Source: Physical constant.
Propane in a 20-lb tank 20 lb
A full "20-lb" grill tank holds 20 lb of propane.
Plausible range: 17–20. Source: DOT cylinder rating.
Solar system losses 75%
Real harvest vs. panel rating: heat, angle, dirt, wiring, charge-controller and battery-charging losses.
Plausible range: 65–85%. Source: NREL PVWatts default system losses plus charging loss.
Default peak sun hours 4.5 hours a day
Peak sun hours a day used when you don’t pick your own: about a US average. Cloudy winter days give about 2, sunny summer days about 6.
Plausible range: 2–6. Source: NREL solar resource maps (US average roughly 4–5 peak sun hours).
Planning margin 1.25×
Recommended sizes are 25% above the computed need. Not applied to runtime estimates.
Source: Standard sizing practice.
Power station charging efficiency 90%to be measured
Share of the watts a power station draws from the wall or a generator that ends up stored in its battery.
Plausible range: 85–95%. Source: Typical AC charger efficiency (specs/calculator-suite.md §11.5).
Medical planning multiplier 2×
For medical devices we recommend capacity for twice the nights asked for.
Source: Our policy for life-support and medical loads.
Default duty cycle 40%
Fallback when a cycling appliance has no duty cycle. Higher in hot rooms and right after power returns.
Plausible range: 30–50%. Source: Typical compressor duty cycles.
Starting watts, compressor 3 × running watts
Fallback starting watts for a compressor with no data.
Plausible range: 2–5. Source: Typical locked-rotor vs running current for small compressors.
Starting watts, pump or blower motor 2.5 × running watts
Fallback starting watts for pumps, blowers and other induction motors (also used for universal motors).
Plausible range: 2–3.5. Source: Generator-maker wattage charts.
Starting watts, inverter-drive compressor 1.2 × running watts
Inverter mini-splits and inverter fridges soft-start.
Plausible range: 1–1.5. Source: Maker specs for inverter-drive compressors.
Share of a sump backup claim we count on 80% of the maker’s claim
Share of a battery-backup sump pump maker's runtime claim we count on. Claims assume a new, fully charged battery run to cutoff; a battery that has sat on standby for a few years holds less.
Plausible range: 70–100%. Source: Our policy (round toward safety); matches the 80% emergency depth of discharge used for lead-acid.
BTU per watt 3.412 BTU/h per W
1 W of heat is 3.412 BTU/h.
Source: Physical constant.
Default air conditioner efficiency 11 BTU/h per W
Default efficiency (EER/CEER) for converting an air conditioner’s BTU rating to watts.
Plausible range: 9–15. Source: Energy Star room AC minimums are about CEER 10–12.
Starting surge a soft starter removes 65% of starting wattsto be measured
A soft-start kit on a central air conditioner or heat pump ramps the compressor up instead of slamming it on. With one fitted, starting watts = the larger of running watts or starting watts × (1 − 0.65).
Plausible range: 50–75%. Source: Soft-starter makers claim 50–75% less inrush current; we use a middle value. Ask the installer for your unit’s measured figure.
Heat in a cubic foot of natural gas 1,036 BTU per ft³
Converts a standby generator’s natural-gas use (ft³/h) into therms on your gas bill, and gas appliances’ BTU ratings into ft³/h for the gas meter check.
Plausible range: 1,000–1,100. Source: U.S. EIA average heat content of natural gas delivered to consumers (about 1,036 BTU/ft³ in recent years).
BTU per therm 100,000 BTU
Gas bills charge per therm, which is 100,000 BTU.
Source: Definition.
Usable share of a propane tank 80%
Large propane tanks are filled to about 80% to leave room for the liquid to expand, so a 500-gallon tank holds about 400 gallons.
Plausible range: 70–85%. Source: Standard propane delivery practice (NFPA 58 fill limits).
Typical home gas meter capacity 250 ft³/hto be measured
A common residential natural-gas meter passes about 250 ft³ an hour. A large standby generator at full load plus a furnace and water heater can need more, so the sizer flags it and suggests asking the gas utility.
Plausible range: 175–425. Source: Typical residential diaphragm meter ratings; your utility sets the real figure.
Gas furnace input (for the meter check) 80,000 BTU/h
Typical home gas furnace input rating, used only for the gas meter check.
Plausible range: 40,000–120,000. Source: Typical nameplate inputs; use your furnace’s label.
Gas water heater input (for the meter check) 40,000 BTU/h
Typical tank water heater input; tankless units can be 150,000–199,000.
Plausible range: 30,000–199,000. Source: Typical nameplate inputs; use your water heater’s label.
Gas range input (for the meter check) 65,000 BTU/h
All burners and the oven of a typical gas range, used only for the gas meter check.
Plausible range: 40,000–90,000. Source: Typical nameplate inputs.
Gas dryer input (for the meter check) 22,000 BTU/h
Typical gas clothes dryer input, used only for the gas meter check.
Plausible range: 20,000–35,000. Source: Typical nameplate inputs.
Home battery discharge efficiency 95%
Loss between a home battery and your outlets. When the maker publishes a round-trip efficiency (about 0.88–0.90), we use its square root instead, since an outage only uses the discharge half.
Plausible range: 92–97%. Source: Square root of published round-trip efficiencies (Tesla, Enphase, FranklinWH, Generac datasheets).
Home battery standby draw 30 W per unitto be measured
Power each battery’s inverter and controls use just by being on during an outage. Makers don’t publish it.
Plausible range: 10–60. Source: Estimate. To be checked against owner data.
Lithium-ion cell voltage 3.7 V
Nominal voltage of one lithium-ion cell, which power banks and phones use when they quote capacity in mAh.
Plausible range: 3.6–3.85. Source: Typical nominal Li-ion cell voltage on power bank labels.
What the math can't know
Your appliance may draw more or less than the typical figure, a battery's real capacity drops with age and cold, and a storm may make your sump pump run harder than any default. Treat our results as a planning estimate. When it matters, measure your own appliances with a plug-in power meter, and leave a margin. Found a mistake? Tell us via theAbout page.