Whole-Home Backup Sizer: Generator or Battery
Tell us about your house. See what a standby generator or a home battery system needs to cover essentials or the whole home, and what a smaller essentials setup would take instead.
How we make money: some links on this page go to stores that may pay us a commission if you buy. It doesn't change the price you pay or which product we recommend; we rank by fit first. Details
What your house needs
- Running at once (peak)
- 2,242 W
- Energy a day
- 8.8 kWh (26.5 kWh over 3 days)
- A 200 A panel would suggest
- 48,000 W: about 21.4× what this list runs
Show the math
- Fridge: average draw: 500 kWh a year × 1,000 ÷ 8,760 h (Energy Star label) = 57.1 W
- LED bulb: average draw: 9 W × 6 = 54 W
- Router: average draw: 10 W = 10 W
- Modem: average draw: 8 W = 8 W
- Phone: average draw: 20 W × 2 = 40 W
- Microwave: average draw: 1,400 W = 1,400 W
- TV: average draw: 80 W = 80 W
- Furnace fan: average draw: 500 W × 0.5 duty cycle = 250 W
- Energy a day: 57.1 W × 24 h + 54 W × 5 h + 10 W × 24 h + 8 W × 24 h + 40 W × 2 h + 1,400 W × 0.3 h + 80 W × 4 h + 250 W × 24 h = 8,822 Wh
- Average over the day: 8,822 Wh ÷ 24 h = 367.6 W
- Peak running watts: 150 W + 9 W × 6 + 10 W + 8 W + 20 W × 2 + 1,400 W + 80 W + 500 W = 2,242 W
- Peak starting watts: 2,242 W + 900 W extra while the Furnace fan starts (one motor starts at a time) = 3,142 W
A. Standby generator
Installed outside on a concrete pad, runs on natural gas or propane, and starts by itself through an automatic transfer switch. Runs for days on a gas line; needs a yearly service.
Look for at least 3,150 W of running watts (the 10 kW class covers the running load). Makers don't publish starting figures for these units, so we make the running rating cover your biggest start as well.
Generac Guardian 10 kW
9,000 W on natural gas · about 2,424 ft³ (25.1 therms) a day
Gas meter: at full load this unit plus your gas furnace, water heater, range, dryer could draw about 327 ft³/h, more than a typical 250 ft³/h home meter. Ask your gas utility.
Generac Guardian 14 kW
14,000 W on natural gas · about 4,680 ft³ (48.5 therms) a day
Gas meter: at full load this unit plus your gas furnace, water heater, range, dryer could draw about 456 ft³/h, more than a typical 250 ft³/h home meter. Ask your gas utility.
Generac Guardian 18 kW
17,000 W on natural gas · about 3,936 ft³ (40.8 therms) a day
Gas meter: at full load this unit plus your gas furnace, water heater, range, dryer could draw about 435 ft³/h, more than a typical 250 ft³/h home meter. Ask your gas utility.
Show the math
- Peak running watts: 150 W + 9 W × 6 + 10 W + 8 W + 20 W × 2 + 1,400 W + 80 W + 500 W = 2,242 W
- Peak starting watts: 2,242 W + 900 W extra while the Furnace fan starts (one motor starts at a time) = 3,142 W
- Running watts needed: 2,242 W ÷ 0.8 (keep it under 80% load) = 2,803 W
- Standby size class: smallest of 10 / 14 / 18 / 22 / 26 kW covering 2,850 W = 10 kW
- Load on the generator: 368 W average ÷ 9,000 W rated = 10%
- Fuel curve from the maker’s claims: 101 ft³/h at 50% load; 127 ft³/h at 100% load = 75 + 52 × load ft³/h
- Gas an hour: maker's 50%-load figure (none published below that) = 101 ft³/h
- Therms a day: 2,424 ft³ × 1,036 BTU ÷ 100,000 = 25.1 therms
- Gas meter check: 127 ft³/h generator at full load + 200 ft³/h other gas appliances vs 250 ft³/h typical meter = ask your gas utility
Assumptions used: Generator load limit; Heat in a cubic foot of natural gas; Typical home gas meter capacity; Usable share of a propane tank; Propane weight per gallon. What these mean
B. Home batteries
Wall batteries such as a Powerwall, installed with a gateway or backup switch. Silent, switch over automatically, no fuel. Without solar, they have to hold the whole outage, so long outages and big loads need many units.
Only works in an outage with a battery or backup-capable inverter.
| System for 3 days | Set by | Usable | Lasts (no sun) | Installed, before incentives |
|---|---|---|---|---|
| 1 × Tesla Powerwall 3 + 2 × Powerwall 3 Expansion | energy for the outage | 40.5 kWh | 4 days | about $39,200 |
| 3 × FranklinWH aPower 2 | energy for the outage | 45 kWh | 3.9 days | about $55,400 |
| 5 × Enphase IQ Battery 10C | energy for the outage | 50 kWh | 3.8 days | about $71,500 |
| 16 × Enphase IQ Battery 5P | energy for the outage | 80 kWh | 3.8 days | about $114,300 |
| 2 × Generac PWRcell 2 Short of the outage plus our 25% margin at the maker's 36 kWh limit | energy for the outage | 36 kWh | 3.3 days | ask an installer |
Costs are typical installed prices from EnergySage's 2026 quote data, before any incentives. The federal 30% credit ended for systems installed after 2025; check your state and utility. Usable energy is the maker's figure; we assume the batteries are full when the outage starts.
Show the math
- Units for running watts: 2,242 W ÷ 11,500 W per unit = 1
- Units for starting watts: 3,142 W ÷ (185 A LRA × 240 V) per unit = 1
- Energy needed: 1.25 margin × max(one day, 3 days × (10,071 Wh a day)) = 37,767 Wh
- Battery drain: 368 W average ÷ 0.943 + 1 × 30 W standby = 420 W
- System: 1 × 13.5 kWh + 2 × 13.5 kWh expansion = 40.5 kWh
Assumptions used: Home battery discharge efficiency; Home battery standby draw; Planning margin; Solar system losses. What these mean
C. Just the essentials, for much less
Backing up only the fridge, lights, internet, the furnace or boiler and a few outlets takes about 3,142 W starting and 8.8 kWh a day. A portable generator or a large power station on a transfer switch or interlock covers that for a fraction of the cost.
Compare a power station, generator and hybrid for these essentials · Size a portable generator
Side by side
| Standby generator | Home batteries | |
|---|---|---|
| For this list | Generac Guardian 10 kW | 1 × Tesla Powerwall 3 + 2 × Powerwall 3 Expansion |
| Upfront | unit from $3,600, plus installation, transfer switch and gas line | about $39,200 installed |
| How long | As long as the gas flows | 4 days |
| Starts by itself | Yes, after a short delay while the engine starts | Yes; some switch over without a flicker |
| Upkeep | Yearly service and oil changes; runs a short self-test on a schedule | Almost none; also cuts bills with solar |
Both need a licensed electrician (and a plumber for the gas line) and usually a permit. The transfer switch or backup gateway keeps the house disconnected from the grid while it's on backup power: never back-feed a house through an outlet. Keep a standby generator at the maker's clearances from windows, doors and vents, and keep CO alarms inside.
Ranked by fit, then installed cost; links go to each maker's page. Product data checked 2026-11-20.
How this is calculated
Start from loads, not panel amps
We build a list from your house: essentials (fridge, lights, internet, microwave, TV and the heating system's fan or pump) or the whole home (adding central air or heat pump, laundry, dishwasher, electric water heater and range if you have them). You can edit the list. Running watts add up; the starting surge is the running total plus the biggest single motor start, since motors are assumed to start one at a time (a load manager makes sure of that). A 200 A panel would suggest 48,000 W, which is a breaker limit, not a load.
Standby generators
The generator's running rating must cover your running watts with 80% headroom, scaled up for elevation. Standby makers don't publish starting (surge) figures, so the running rating must also cover your biggest start. A soft starter on central air or a heat pump cuts that start by about 65%. Fuel use follows the line through the maker's published 50% and 100% load figures; below half load we use the half-load figure rather than guess. Natural gas is converted to therms at 1,036 BTU per ft³; propane tanks count 80% of their size. The gas meter check adds the generator at full load to your gas furnace, water heater, range and dryer at full fire, and flags totals above a typical 250 ft³/h meter.
Home batteries
Each system needs enough units for three things: your running watts (continuous kW per unit), your biggest start (the maker's locked-rotor amps × 240 V) and the energy for the outage with a 25% margin. The page says which one set the count. Energy-only expansion units are added before more full units. Battery drain is the average load ÷ the discharge efficiency (the square root of the maker's round-trip efficiency) plus about 30 W of standby draw per unit. With rooftop solar, the battery must hold at least one full day and the outage's shortfall after solar (panel kW × sun hours × 0.75). Installed costs are EnergySage's 2026 averages before incentives.
Full formulas and default assumptions: How the math works.
Related
- Whole-home battery backup: how many kWh you need and what it costs
- What size generator do I need for my house? (portable generators by household tier)
- Outage Plan Builder (power station, portable generator or hybrid for your essentials)
- Generator Size & Fuel Calculator
- How to keep heat on in a winter power outage
- What size generator to run an air conditioner
- Running watts vs starting watts
- Generator safety: carbon monoxide and transfer switches
Questions people ask
What size generator do I need to run my whole house?
Size it from what runs, not from the panel. A typical gas-heated house with 3-ton central air, a fridge, lights, a washer and the usual kitchen loads runs about 8,940 W at once and needs 20,740 W for a moment when the air conditioner starts. Because standby makers don't publish starting figures, we size so the running rating covers that start: a Generac Guardian 22 kW. With a soft starter on the AC, a Generac Guardian 14 kW covers it.
What size generator do I need for a 200 amp service?
The panel size doesn't tell you. 200 A × 240 V is 48,000 W, but that's the most the breaker allows, not what the house uses: the whole-home example above peaks at about 20,740 W. Sizing to the panel would mean a generator roughly 2–5 times bigger than needed. List what you'll run instead.
How many Powerwalls do I need?
For essentials in winter (fridge, lights, internet, TV, microwave and a gas furnace's blower, about 8.8 kWh a day), one Powerwall 3 covers a day. A whole house with central air uses about 28.9 kWh a day; with 8 kW of rooftop solar and 4.5 sun hours, one Powerwall 3 plus 2 Expansions gets it through. Without solar, a multi-day whole-home outage takes far more batteries than most people buy.
How much natural gas does a standby generator use?
Generac publishes 221 ft³ an hour at half load and 327 ft³ at full load for its 22 kW Guardian. At half load around the clock, that's about 54.9 therms a day. Most houses run well under half load most of the time, but makers don't publish lighter-load figures, so we use the half-load rate as the floor.
Is a home battery or a standby generator better for outages?
A standby generator on natural gas runs as long as the gas flows, so it suits long outages and big loads like central air or electric heat. Home batteries are silent, switch over faster and cut bills with solar, but without solar they only last as long as they hold. Many homes back up essentials with either for much less than whole-home backup.